RAPO® Natural Ester Insulating Oil Standard Values
Performance RAPO® RAPO® 3040 IEC 62770-2013 Test Method
Moisture 36 45 ≤200 IEC 60814
Kinematic Viscosity/(mm²/s) 33.35 36.62 ≤50 ISO 3104
Kinematic Viscosity/(mm²/s) 7.886 8.414 ≤15 ISO 3104
Relative Density (20℃)/(kg·m³) 920.7 917.7 ≤1000 ISO 12185
Pour Point/℃ -18 -30 ≤-10 ISO 3016
Flash Point (Open Cup)/℃ 322 331 ISO 2592
Fire Point/℃ 360 358 ≥300 ISO 2592
Breakdown Voltage (2.5mmHg)/kV 79.1 73.1 ≥35 IEC 60156
Dissipation Factor (90℃)/% 0.68 0.34 ≤5 IEC 60247
Acid Number/(mg KOH/g) 0.015 0.02 ≤0.06 IEC 62021-3
Corrosive Sulfur Non-corrosive Non-corrosive Non-corrosive IEC 62535
DBDS (Dibenzyl Disulfide) Not detected Not detected Not detected IEC 62697-1
PCB Content/ppm Not detected Not detected Not detected IEC 61629
Oxidation Stability (120℃, 48 hours) NB/SH/T 0811
Total Acid Number (as KOH)/(mg/g) 0.17 0.13 ≤0.6 IEC 61125
Kinematic Viscosity (40℃) Increase Rate from Initial Value 22.84% 18.08% ≤30% ISO 3104
Dissipation Factor (90℃) 0.103 0.063 ≤0.5 IEC 60247

Comparison of RAPO® Natural Ester Insulating Oil and Mineral Insulating Oil
RAPO® Natural Ester Insulating Oil Mineral Insulating Oil
Raw Material Oilseed crops Petroleum by-products
Flash Point/℃ ≥350 ≤160
Breakdown Voltage (kV/2.5mm) ≥60 ≥40
Moisture Content (PPM) ≤300 ≤30
Relative Permittivity 3.2 2.2
Biodegradability 98% or more Less than 30%
Volatility Low High
Reliability High Low
Safety High Low
Flame Retardancy Self-extinguishing Combustion-promoting
Waste Disposal Environmentally friendly oil Hazardous waste
Carbon Emission Level K/55 K
Application Examples of RAPO® Natural Ester Insulating Oil